Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/09/2011 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 04/26/2011 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 742 W. GLENN ST: 1) GFCI PROTECT KITCHEN OUTLETS 2) SUB PANEL 30 AMP HOT LEAD MUST BE RED OR BLACK (TAPE OK) 3) RELOCATE ANY SMOKE ALARM WITHIN 36" FORCED AIR REGISTER 4) EXPOSED WIRING LIVING ROOM CEILING 744 W. GLENN ST: 1) GFCI PROTECT KITCHEN OUTLETS 2) BLACK OR RED (TAPE OK) WHITE HOT LEADS 3) RELOCATE SMOKE ALARMS WITHIN 36" REGISTER |