Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - SERVICE UPGRADE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/18/2011 | ELECTRIC - SERVICE UPGRADE | Approved | IVRS - Inspection :* | |
| 05/16/2011 | ELECTRIC - SERVICE UPGRADE | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1) BONDS BUSHING ON SUPPLY SIDE OF MAIN SERVICE FEEDERS 250.92 NEC 2) USE LISTED RISER SUPPORT 110.3 NEC 3) OK WATER, GROUND RODS-NEED TO BOND GAS |