| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/08/2011 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 05/16/2011 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) NEUTRAL AT SUB PANEL NOT TO BE BONDED 2) BRING IN GROUND WIRE TO GROUND BAR |
|
| 05/13/2011 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* | |
| 04/27/2011 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* STILL NEED APPROVED BLANK OFFS FOR PANEL | |
| 04/25/2011 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* | |
| 04/18/2011 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1) FILL IN MISSING BREAKER OPENINGS IN CIRCUIT PANEL WITH APPROVED BLANK OFFS 2) RECEPTS AT COUNTER TOPS WITH SINKS REQUIRED TO BE GFI PROTECTED 3) REPAIR BROKEN CONDUIT TO A/C UNIT |