Inspection History Details
Inspection Status: Denied
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/26/2012 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) MISSING PANEL COVER INSIDE-REPLACE ASAP (SAFETY HAZARD) |
|
| 02/24/2012 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* 1) GROUND ALL DEVICES 2) CALL FOR FINAL AFTER POWER ON AND POWER CHECKED BY ELECTRICIAN 3) CHECK LIGHT FIXTURE OUTSIDE |
|
| 02/13/2012 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1) OK TO CLEAR INCR 2) COMPLETE INSIDE-OK WALLS |
|
| 01/20/2012 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) NO COMPLIANCE WITH ALL NOTES 2) A REINSPECTION FEE WILL BE ASSESED NEXT INSPECTION, IF NO COMPLIANCE 3) REVISE PERMIT FOR SERVICE UPGRADE |
|
| 03/31/2011 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) POST ADDRESS, UNIT MUST BE OPEN FOR INSPECTION. ALSO INSTALL PERMANENT ADDRESS LABEL ON SERVICE EQUIP. (ELECTRIC) 2) OBTAIN THE SERVICES OF A LICENSED CONTRACTOR OR ELECTRICIAN TO REPAIR NUMEROUS CODE VIOLATIONS SUCH AS: EXPOSED WIRING AND SPLICES, UNSUPPORTED CONDUITS, CABLES, BROKEN LIGHT FIXTURES THROUGHOUT BLDG. SERVICE EQUIPMENT NOT RATED FOR LOAD SERVED. 30 AMP METER BASE AND WIRING CONNECTED TO 100 AMP BREAKER-UPGRADE SERVICE AND ASSOCIATED EQUIPMENT 3) ALL WIRING NOT TO CODE OBTAIN PERMIT & PLANS AND START OVER |