Permit: T11EL00914

Parcel: 120086820


Addresses:

4782 S 12TH AV

Inspection Status: Denied

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
04/26/2012 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) MISSING PANEL COVER INSIDE-REPLACE ASAP (SAFETY HAZARD)
02/24/2012 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
1) GROUND ALL DEVICES
2) CALL FOR FINAL AFTER POWER ON AND POWER CHECKED BY ELECTRICIAN
3) CHECK LIGHT FIXTURE OUTSIDE
02/13/2012 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1) OK TO CLEAR INCR
2) COMPLETE INSIDE-OK WALLS
01/20/2012 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) NO COMPLIANCE WITH ALL NOTES
2) A REINSPECTION FEE WILL BE ASSESED NEXT INSPECTION, IF NO COMPLIANCE
3) REVISE PERMIT FOR SERVICE UPGRADE
03/31/2011 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) POST ADDRESS, UNIT MUST BE OPEN FOR INSPECTION. ALSO INSTALL PERMANENT ADDRESS LABEL ON SERVICE EQUIP. (ELECTRIC)
2) OBTAIN THE SERVICES OF A LICENSED CONTRACTOR OR ELECTRICIAN TO REPAIR NUMEROUS CODE VIOLATIONS SUCH AS: EXPOSED WIRING AND SPLICES, UNSUPPORTED CONDUITS, CABLES, BROKEN LIGHT FIXTURES THROUGHOUT BLDG. SERVICE EQUIPMENT NOT RATED FOR LOAD SERVED. 30 AMP METER BASE AND WIRING CONNECTED TO 100 AMP BREAKER-UPGRADE SERVICE AND ASSOCIATED EQUIPMENT
3) ALL WIRING NOT TO CODE OBTAIN PERMIT & PLANS AND START OVER