Permit: T11EL00914

Parcel: 120086820


Addresses:

4782 S 12TH AV

Inspection Status: Approved

Inspection History: ELECTRIC - SERVICE UPGRADE

Date Description Inspector Results Comments
02/13/2012 ELECTRIC - SERVICE UPGRADE Approved IVRS - Inspection :*
02/06/2012 ELECTRIC - SERVICE UPGRADE Denied IVRS - Inspection :
A reinspection fee has been assessed for this inspection. Multiple inspectio
1) LOOSE FITTINGS (CONNECTORS)
2) TEP WILL REQUIRE A 2" RIGID RISER PER SR MANUAL. ALSO BE ADVISED THAT OVERHEAD LINES OVER DRIVEWAY AND OR PARKING AREAS NEED TO BE 18' ABOVE GROUND PER 230 NEC
3) CONNECTOR AT TOP OF SUB-PANEL IS BREAKING THRU THE CONCENTRIC KO
02/02/2012 ELECTRIC - SERVICE UPGRADE Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1) CANNOT USE SMASHED EMT CONDUIT FOR RISER BRACE, MUST BE LISTED SUPPORT
2) 1 1/4" CONDUIT CONNECTOR ON LB NOT RATED FOR OUTDOOR USE
3) GROUND WIRE IN SUB PANEL NEEDS TO BE I.D. GREEN
4) PLUG ALL UNUSED OPENINGS IN PANELS, BOXES, ETC...
5) REINSPECTION FEE NEXT INSPECTION IF NOT CORRECTED, SEE NOTES #3 LAST INSPECTION AND #2 3/31/11