Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - SERVICE UPGRADE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/13/2012 | ELECTRIC - SERVICE UPGRADE | Approved | IVRS - Inspection :* | |
| 02/06/2012 | ELECTRIC - SERVICE UPGRADE | Denied | IVRS - Inspection : A reinspection fee has been assessed for this inspection. Multiple inspectio 1) LOOSE FITTINGS (CONNECTORS) 2) TEP WILL REQUIRE A 2" RIGID RISER PER SR MANUAL. ALSO BE ADVISED THAT OVERHEAD LINES OVER DRIVEWAY AND OR PARKING AREAS NEED TO BE 18' ABOVE GROUND PER 230 NEC 3) CONNECTOR AT TOP OF SUB-PANEL IS BREAKING THRU THE CONCENTRIC KO |
|
| 02/02/2012 | ELECTRIC - SERVICE UPGRADE | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1) CANNOT USE SMASHED EMT CONDUIT FOR RISER BRACE, MUST BE LISTED SUPPORT 2) 1 1/4" CONDUIT CONNECTOR ON LB NOT RATED FOR OUTDOOR USE 3) GROUND WIRE IN SUB PANEL NEEDS TO BE I.D. GREEN 4) PLUG ALL UNUSED OPENINGS IN PANELS, BOXES, ETC... 5) REINSPECTION FEE NEXT INSPECTION IF NOT CORRECTED, SEE NOTES #3 LAST INSPECTION AND #2 3/31/11 |