Permit: T11EL00795

Parcel: 112033510


Addresses:

3245 N PALMER DR

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
05/17/2011 ELECTRIC - FINAL Approved IVRS - Inspection :*
03/30/2011 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) NEED LICENSED ELECTRICIAN TO MAKE COMPLETE EVALUATION OF ELECTRICAL SYSTEM AND MAKE CORRECTIONS AS NECESSARY
IE:
1) CLOSET SUB PANEL COMPONENTS
2) N.E. BED CLOSET WERE LIGHT HAS CHARRED THE ADJACENT COMBUSTIBLES
3) LIVING ROOM CLOSET LIGHT THAT UTILIZES UNPROTECTED ROMEX THROUGH AND UP EXTERIOR OF WALL
4) 3 PRONG OUTLETS ON A 2 WIRE SYSTEM
5) POINTED SCREWS IN SUB PANEL COVER AND NO SCREW IN MAIN PANEL
6) INTERIOR EXTENSION CORDS OUTSIDE
7) SPOT LIGHTS NOT POINTING AT 45 DEGREE OR LESS
8) ANY OTHER PROBLEMS FOUND AND GIVE WRITTEN DESCRIPTION ON HIS/HER LETTERHEAD