Permit: T11EL00792

Parcel: 131071980


Addresses:

6241 E 28TH ST

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
04/19/2011 ELECTRIC - FINAL Approved IVRS - Inspection :*
03/22/2011 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1 SMOKE DETECTORS NEEDED IN ALL BEDROOMS AND ADJACENT HALL
2) EXPOSE PANEL GROUNDING CONDUCTOR (CUT 4 AWG BELOW PANEL)
3) CAP UNUSED KNOCKOUTS AT PANEL
4) GFI PROTECT KITCHEN COUNTER RECEPTS
NOTE: DETACHED ACCRESSORY BLDG 10 X 13 APPEARS TO HAVE BEEN BUILT WITHOUT PERMIT