Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/18/2011 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* 1) NOTE TO TEP-PLEASE RE-ATTACH GUY WIRE SUPPORT TO INSULATER |
|
| 03/25/2011 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) WIRING ON ROOF NOT TO CODE, UF CABLE HOOK UP TO RECEPT WITHOUT BOX. ALSO ROOF RECEPT NEEDS TO BE GFI PROTECTED 2) INSULATOR FOR GUY SUPPORT (TRI PLEX) PULLED OUT OF ROOF. PLUG HOLE ON TOP OF SERVICE DISCONNECT 3) DBL LUGGING IN SERVICE DISC. SW. |