Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/04/2011 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 04/21/2011 | ELECTRIC - FINAL | Partial Approval | PENDING T11CM00852 | |
| 03/22/2011 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) RELOCATE ANY SMOKE ALARM WITHIN 36" FORCED AIR REGISTER 2) ADDED CIRCUITS AT PANEL CONDUIT NOT TO CODE WEATHERED FITTINGS REQUIRED. PROVIDE SEALED FITTINGS AT PANEL 3) PROVIDE PROOF OF PERMIT AND INSPECTIONS REAR ADDITION TO INCLUDE FIRE SEPERATION 4) LABEL CIRCUIT PANEL |