Inspection History Details
Inspection Status: Not ready for Inspection
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/29/2011 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* 1) SEAL KNOCK OUT HOLE IN SIDE OF BOX 2) SPOKE WITH R. CAMACHO REGARDING NOTES |
|
| 03/21/2011 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) PROVIDE SEPERATE GROUND, YOU MAY NOT SHEAR GROUNDS. GROUND ROD SYSTEM 2) MEANS OF DISCONNECT ABOVE 67" HIGHEST BREAKER 3) MAINTAIN WORKING CLEARANCE IN FRONT OF SERVICE 4) REPLACE PLYWOOD AT METER BASE AND SECURE BASE PROPERTY 5) PROVIDE CONTACT TEP FOR DUMMY RISER 2" OR SERVICE MAY HAVE TO BE INCREASED WITH 2" RISER. NO INCREASE AT THIS TIME 7) REPLACED FIRE DAMAGE BOX FUSE TYPE TO BREAKERS |