Permit: T11EL00776

Parcel: 132090010

Inspection Status: Not ready for Inspection

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
03/29/2011 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
1) SEAL KNOCK OUT HOLE IN SIDE OF BOX
2) SPOKE WITH R. CAMACHO REGARDING NOTES
03/21/2011 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) PROVIDE SEPERATE GROUND, YOU MAY NOT SHEAR GROUNDS. GROUND ROD SYSTEM
2) MEANS OF DISCONNECT ABOVE 67" HIGHEST BREAKER
3) MAINTAIN WORKING CLEARANCE IN FRONT OF SERVICE
4) REPLACE PLYWOOD AT METER BASE AND SECURE BASE PROPERTY
5) PROVIDE CONTACT TEP FOR DUMMY RISER 2" OR SERVICE MAY HAVE TO BE INCREASED WITH 2" RISER. NO INCREASE AT THIS TIME
7) REPLACED FIRE DAMAGE BOX FUSE TYPE TO BREAKERS