Permit: T11EL00725

Parcel: 133382840

Inspection Status: Approved

Inspection History: ELECTRIC - SERVICE UPGRADE

Date Description Inspector Results Comments
07/26/2011 ELECTRIC - SERVICE UPGRADE Approved IVRS - Inspection :*
07/21/2011 ELECTRIC - SERVICE UPGRADE Denied 1) MAXIMUM OVER CURRENT PROTECTION FOR 12 AWG WIRE IS 20 AMPS
2) BOND BUSHING NEEDED FOR METAL CONDUIT TO DISCONNECT ALONG SIDE PANEL
3) LABEL CIRCUITS AT PANEL
4) BREAKERS MUST BE OF SAME MAKE AS PANEL MANUFACTURE