Permit: T11EL00629

Parcel: 116260390

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
07/15/2011 ELECTRIC - FINAL Approved IVRS - Inspection :*
03/07/2011 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) ADDED LIGHT FIXTURES EXTERIOR NOT TO CODE. EXPOSED ROMEX
2) MIXED BREAKER TYPES IN PANEL MUST MATCH PANEL TYPE
3) EXSPOSED WIRING IN STORAGE ROOM. PROVIDE PROOF OF PERMIT FOR ELECTRIC OR OMIT ALL ELECTRIC OR PERMIT
4) GARAGE REQUIRES FIRE SEPERATION FROM ? GARAGE EAST WALL AND SOUTH WALL
5) GFCI PRTOECT KITCHEN COUNTER OUTLETS AND BATH OUTLETS
6) SMOKE ALARMS BEDROOMS
7) BEDROOM WINDOW SECURITY BARS MUST OPERATE FREELY WITHOUT USE OF SEPERATE TOOLS
8) WATER HEATER TPR VALVE CAPPED/MUST DRAIN TO EXTERIOR OR PAN WITH 3/4" COPPER OR CVPC