Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/18/2012 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 04/17/2012 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
| 03/22/2011 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) FURNACE FLEX MAY NOT PENETRATE CABINET MUST BE HARD PIPED THRU PENETRATION 2) EXTEND TPR LINE TO EXTERIOR 6"-24" FROM GROUND 3) COVER PLATES MISSING THROUGHOUT-MISSING OUTLETS 4) SECURE 220 STOVE PER CODE 5) HAZARDOUS WIRING AT STOVE EXHAUST FAN 6) SMOKE ALARM BEDROOMS AND HALLWAY 7) OMIT DBL KEYED DEAD BOLTS EXIT DOOR 8) SECURE PANEL TO WALL PER CODE 9) SEAL KNOCKOUTS BOTTOM PANEL 10) SHARED NEUTRAL WIRES BUSS ONE PER SCREW 11) PROVIDE PROOF OF PERMIT REAR PORCH WITH ELECTRICAL ON WEST PROPERTY LINE. HEADER OVERSPANNED 12) MISSING LIGHT FIXTURES EXPOSED WIRING |
|
| 03/16/2011 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) POST HOUSE NUMBERS 2) PROVIDE ACCESS TO STORAGE AND MECH ROOMS AT CARPORT 3) KEY IN LOCK BOX DOES NOT OPEN FRONT DOOR DEAD BOLT 4) NEXT DENIAL MAY RESULT IN REFEE |
|