Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T11EL00608
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
04/14/2011 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
04/07/2011 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
03/23/2011 | ELECTRIC - FINAL | Denied | IVRS - Inspection : 1. BONDING SCREW IN DISCONNECT MISSING 2. NEUTRAL BONDING JUMPER IN METER BASE TO BE BONDED 3. 2 1/2 RIGID ON METER BASE & DISCONNECT MISSING STRUT STRAP 4. DISCONNECT MISSING REJECTION CLIPS 5. GROUND RODS AT SERVICE BOTH HAVE ENDS CUT - WHY??? |