Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - UFER
Permit Number - T11EL00573
Inspection Description - ELECTRIC - UFER
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
03/17/2011 | ELECTRIC - UFER | Approved | ||
03/11/2011 | ELECTRIC - UFER | Cancelled | IVRS - RI canceled | |
03/09/2011 | ELECTRIC - UFER | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) VERIFY PERMIT FOR NEW WORK TO INTERIOR 2) MAIN BONDING JUMPER TO BE SAFE SIZE AS GEC 3) CANNOT USE SHEET METAL THREAD SCREWS FOR GROUNDING 250.8 4) NEED REJECTION PINS 5) VERIFY ELECTRODE GROUND FAULT PATH WITH CHASE NIPPLE 6) PLANS CALL FOR XHAW-THWN/THHN INSTALLED 7) WATER BOND CALLS FOR #2 BC NOT #4 |