Permit: T11EL00573

Parcel: 117160030


Addresses:

119 E TOOLE AV #101


Inspection Status: Approved

Inspection History: ELECTRIC - UFER

Permit Number - T11EL00573

Inspection Description - ELECTRIC - UFER

Inspection Status - Approved

Date Description Inspector Results Comments
03/17/2011 ELECTRIC - UFER Approved
03/11/2011 ELECTRIC - UFER Cancelled IVRS - RI canceled
03/09/2011 ELECTRIC - UFER Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) VERIFY PERMIT FOR NEW WORK TO INTERIOR
2) MAIN BONDING JUMPER TO BE SAFE SIZE AS GEC
3) CANNOT USE SHEET METAL THREAD SCREWS FOR GROUNDING 250.8
4) NEED REJECTION PINS
5) VERIFY ELECTRODE GROUND FAULT PATH WITH CHASE NIPPLE
6) PLANS CALL FOR XHAW-THWN/THHN INSTALLED
7) WATER BOND CALLS FOR #2 BC NOT #4