Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/31/2011 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 10/13/2011 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1) RISER SUPPORTS TO BE 1/4" MINIMUM HARDWARE 2) USE LISTED MAST BRACE KITS 3) SECURE PANEL WITH APPROVED HARDWARE-NOT DRY WALL SCREWS 4) SECURE GROUNDING ELECTRODE TO STRUCTURE 5) SUPPLIMENTAL GROUND ROD TO BE CONNECTED TO MAIN ROD 6) NEED MAIN BREAKERS INSTALLED 7) LABEL SERVICE AND UNITS WITH PERMANENT METAL LABELS 8) VERIFY GAS AND WATER BOND 9) PLEASE VERIFY QUALIFIED ELECTRICAL PERSON 10) WLL NEED 2' EXTEND BEYOND WH FOR TEP |