Permit: T11EL00490

Parcel: 12007422A


Addresses:

4319 S BELMAR AV

Inspection Status: Approved

Inspection History: ELECTRIC - RECONNECT

Date Description Inspector Results Comments
08/18/2011 ELECTRIC - RECONNECT Approved IVRS - Inspection :*
02/23/2011 ELECTRIC - RECONNECT Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) PROVIDE PROOF OF PERMIT ALL PORCHES, NOT BUILT TO CODE. OVERSPANNED RAFTERS 2 X 6 SPAN 11'-24" ON CENTER. 4 X 4 HEADERS SPANS 11', DAMAGED RAFTERS
2) NO WATER SUPPLY TO WATER HEATER EXTEND TPR VALVE 6-24" FROM GROUND
3) PROVIDE PROOF OF PERMIT LAUNDRY ADDED. PLUMBING NOT TO CODE, WITH ADDED 220 TO DRYER. WHITE HOT LEAD MUST BE RED OR BLACK (TAPE OK)
4) LABEL CIRCUITS MAIN PANEL. SEAL KNOCKOUTS
5) HAZARDOUS ELCTRICAL AT REAR PORCH
6) PROOF OF PERMIT REAR PORCH. WHAT IS LEDGER ATTACHEMENT ?
7) GFCI PROTECT KITCHEN OUTLET AT COUNTER TOP
8) EXPOSED ROMEX KITCHEN EXHAUST FAN
9) EXPOSED ROMEX THROUGHOUT AT SWITCHES AND LIGHT FIXTURES
10) SMOKE ALARM BEDROOM AND HALLWAY
11) REAR BEDROOM WINDOWS DO NOT NEET EGRESS REQUIREMENTS