Permit: T11EL00466

Parcel: 127041790


Addresses:

4907 E 4TH ST

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
04/07/2011 ELECTRIC - FINAL Approved IVRS - Inspection :*
03/17/2011 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) GROUND WIRE TO MAIN PANEL HAS BEEN CUT-NEED NEW GROUND RODS (2) 6 FEET APART AND NEW GROUND WIRE TO PANEL
02/22/2011 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) MISSING SMOKE DETECTORS IN BEDROOMS-HALLWAY (BATTERY OK)
2) NEED GFCI PROTECTION ON BATH/KITCHEN COUNTER TOP RECEPTS
3) MISSING FACE PLATES THRU OUT HOME
4) MISSING DEAD FACE AT MAIN SERVICE
5) BREAKERS ARE DBL LUGGED
6) NEED GFCI PROTECTION ON EXTERIOR RECEPTS AND BUBBLE COVERS
7) OUTSIDE WIRING HAS SEVERAL CODE VIOLATIONS