Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/07/2011 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 03/17/2011 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) GROUND WIRE TO MAIN PANEL HAS BEEN CUT-NEED NEW GROUND RODS (2) 6 FEET APART AND NEW GROUND WIRE TO PANEL |
|
| 02/22/2011 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) MISSING SMOKE DETECTORS IN BEDROOMS-HALLWAY (BATTERY OK) 2) NEED GFCI PROTECTION ON BATH/KITCHEN COUNTER TOP RECEPTS 3) MISSING FACE PLATES THRU OUT HOME 4) MISSING DEAD FACE AT MAIN SERVICE 5) BREAKERS ARE DBL LUGGED 6) NEED GFCI PROTECTION ON EXTERIOR RECEPTS AND BUBBLE COVERS 7) OUTSIDE WIRING HAS SEVERAL CODE VIOLATIONS |