Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/11/2011 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 03/07/2011 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1) WHAT DID ELECTRICIAN DO ? 2) USE UV RATED TY RAPS TO SUPPORT #6 BARE |
|
| 02/25/2011 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) A REINSPECTION FEE WILL BE ASSESED NEXT INSPECTION, IF NO COMPLIANCE 2) VERIFY TO INSPECTOR THAT SYSTEM IS GROUNDED-ALSO THERE IS A BLUE WIRE ON NEUTRAL BUSS ? |
|
| 02/23/2011 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) GROUNDS AND NEUTRALS STILL TIED TOGETHER IN SUB PANEL, NO GROUND (EQUIP. GRND) RUN WITH FEEDERS-SEE LAST NOTE ON LAST INSPECTION 2) RE-INSPECTION FEE WILL BE ASSESED NEXT INSPECTION IF NO COMPLIANCE |
|
| 02/16/2011 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
| 02/14/2011 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) INSTALL PERMANENT ADDRESS LABEL ON SERVICE DISCONNECT 2) UNLOCK GATE FOR ACESS INTO SERVICE EQUIPMENT |