Permit: T11EL00250

Parcel: 11308091B

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
03/11/2011 ELECTRIC - FINAL Approved IVRS - Inspection :*
03/10/2011 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
03/08/2011 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
1) #4 REAR LIGHTS CANNOT BE POWERED WITH A CUT OFF EXTENSION CORD
2) RECALL FOR FINAL AFTER LIGHT WIRING IS CORRECTED
02/01/2011 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
DEFICIENCIES 1-5 HAVE NOT BEEN CORRECTED
IF CORRECTIONS ARE NOT DONE BEFORE THE NEXT INSPECTION IS CALLED THERE WILL BE A RE-FEE
01/28/2011 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
NOTE: REAR S.E. EXTERIOR DOOR WAS OPEN INSPECTORS ARRIVAL
REASONS FOR DENIAL:
1) ALL CIRCUITS, IN S.E. BEDROOM CLOSET SUB PANEL, ARE OVERFUSED
2) SUB-PANEL COVER CANNOT UTILIZE POINTED SCREWS FOR ATTACHMENT
3) ALL OUTLETS, SERVED BY THE 2-WIRE CIRCUITS IN SUB PANEL, MUST BE 2 PRONG OUTLETS OR GFI PROTECTED
4) CORRECT IMPROPER WIRING AT REAR EXTERIOR
5) MAIN PANEL DEAD FRONT COVER NEEDS A SCREW
OTHER NOTED DEFICIENCIES:
1) WATER HEATER INSUFFICIENT COMBUSTION/RELIEF AIR
2) S.E. AND W. EXTERIOR DOORS OPEN OUTWARDS TO HIGH STEP DOWNS
3) KITCHEN COUNTER OUTLETS ARE NOT GFI PROTECTED
4) CORRECTIONS FOR 1, 2 AND 3 ARE SUGGESTED