Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/11/2011 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 03/10/2011 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
| 03/08/2011 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* 1) #4 REAR LIGHTS CANNOT BE POWERED WITH A CUT OFF EXTENSION CORD 2) RECALL FOR FINAL AFTER LIGHT WIRING IS CORRECTED |
|
| 02/01/2011 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* DEFICIENCIES 1-5 HAVE NOT BEEN CORRECTED IF CORRECTIONS ARE NOT DONE BEFORE THE NEXT INSPECTION IS CALLED THERE WILL BE A RE-FEE |
|
| 01/28/2011 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* NOTE: REAR S.E. EXTERIOR DOOR WAS OPEN INSPECTORS ARRIVAL REASONS FOR DENIAL: 1) ALL CIRCUITS, IN S.E. BEDROOM CLOSET SUB PANEL, ARE OVERFUSED 2) SUB-PANEL COVER CANNOT UTILIZE POINTED SCREWS FOR ATTACHMENT 3) ALL OUTLETS, SERVED BY THE 2-WIRE CIRCUITS IN SUB PANEL, MUST BE 2 PRONG OUTLETS OR GFI PROTECTED 4) CORRECT IMPROPER WIRING AT REAR EXTERIOR 5) MAIN PANEL DEAD FRONT COVER NEEDS A SCREW OTHER NOTED DEFICIENCIES: 1) WATER HEATER INSUFFICIENT COMBUSTION/RELIEF AIR 2) S.E. AND W. EXTERIOR DOORS OPEN OUTWARDS TO HIGH STEP DOWNS 3) KITCHEN COUNTER OUTLETS ARE NOT GFI PROTECTED 4) CORRECTIONS FOR 1, 2 AND 3 ARE SUGGESTED |