Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/18/2011 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 01/27/2011 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) GFI PROTECTED RECEPTS REQUIRED KITCHEN COUNTER AREA AND BATHROOMS 2) REPLACE POWER CORD FOR FURNACE, EXISTING CORD FRAYED 3) EXPOSED ROMEX IN BATHROOM WHERE CABINET USED TO BE 4) BEDROOMS NEED SMOKE DETECTORS, CEILING FANS NOT WIRED TO CODE (ZIP CORD) 5) EXPOSED ROMEX IN CARPORT, CEILING FAN NOT WIRED TO CODE 6) OUTSIDE BACKYARD HAS EXPOSED WIRING, RECEPTS NEED TO BE GFI PROTECTED 7) UTILITY ELECTRIC ATTACHMENT ON ROOF PULLING OUT. PROVIDE ROOF NEXT INSPECTION 8) USE LICENSED OR QUALIFIED ELECTRICIAN TO DO WORK-RECALL INSPECTION WHEN READY |