Permit: T11EL00047

Parcel: 134171170


Addresses:

7320 E MONTECITO DR

Inspection Status: Approved

Inspection History: ELECTRIC - SERVICE UPGRADE

Date Description Inspector Results Comments
02/23/2011 ELECTRIC - SERVICE UPGRADE Approved IVRS - Inspection :*
01/07/2011 ELECTRIC - SERVICE UPGRADE Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) PANEL TO BE 3' FROM GAS METER
2) OUTLET UNDER PANEL MISSING BUBBLE COVER
3) RISER TO BE RE-STRAPPED TO TEP SR-305 8" FROM WEATHER HEAD
4) WIRES ON RISER TO BE REPLACED AND INSULATION NOT SUN RESISTANT
5) CHASE NIPPLES TO LB TO BE REPLACED NOT MAKING A GOOD BOND
6) PANEL SCHEDULE MISSING
7) COVER UP HOLE ON ROOF AND ROOF TACK MISSING