Inspection History Details
Inspection Status: Partial Approval
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/12/2013 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* | |
| 04/12/2013 | ELECTRIC - FINAL | Partial Approval | 1. 220V OUTLET ON PORCH MISSING COVER 2. PROVIDE WET LOCATION LIGHT OVER SHOWER OR REMOVE |
|
| 03/25/2013 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
| 03/21/2013 | ELECTRIC - FINAL | Denied | IVRS - Inspection : There is no access to the site.| 920* |
|
| 02/28/2011 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1) HIGHEST BREAKER NOT MORE THAN 6' 7" 404.8 (A) 2) GROUNDING ELECTRODE CONDUCTOR INMETAL RACEWAY TO BE PER 250.64 (E) 3) PLEASE VERIFY GROUNDED RODS 4) GROUNDING ELECTRODE CONDUCTOR TO BE TERMINATED TO GROUNDED CONDUCTOR 250.24 5) MAINTAIN WORKING SPACE 110.26 |
|
| 02/25/2011 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* 1) RENTAL UNIT REQUIRES LICENSED CONTRACTOR 2) 3 METER PACK INSTALLED. ONLY ONE ADDRESS ON PERMIT 3) 3 METER PACK SHOULD BE-COMMERCIAL INSPECTOR NOTES RAY MAJUTA TALKED TO RENTER AND INFORMED RENTER THAT NAME AND LICENSE NUMBER OF CONTRACTOR WAS NEEDED, NOT OWNER OCCUPIED AND 1 ADDRES ONLY-NO OTHER CLEARANCE CAN BE GIVEN. THIS PERMIT FOR RECONNECT AND INCREASE |
|
| 02/23/2011 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* 1) LEFT MESSAGE 8:55 AM 2) NO ACCESS, GATE LOCKED 3) NO PAPERWORK FOUND |
|
| 01/06/2011 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* 1) WRONG DESCRIPTION OF WORK 2) RECOMEND UPGRADE TO UNIT 3) POWER ALREADY ENERGIZED 4) MANY ADDED CIRCUITS TO SERVICES NOT TO CODE |