Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - SERVICE UPGRADE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/04/2011 | ELECTRIC - SERVICE UPGRADE | Approved | IVRS - Inspection :* | |
| 02/01/2011 | ELECTRIC - SERVICE UPGRADE | Partial Approval | IVRS - Inspection :* 1. AT SUB PANEL TIGHTEN CONDUCTOR TERMS. |
|
| 01/24/2011 | ELECTRIC - SERVICE UPGRADE | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1) A REINSPECTION FEE MAYBE ASSESED IF ALL ITEMS NOT FINISHED 2) CLEAN SURFACE UNDER GROUND BAR 250.12 3) CANNOT USE SHEET METAL THREAD SCREWS FOR GROUNDING 250.8 4) FINISH #3 PREVIOUS INSPECTION 5) NEW SUB PANEL NOT ALLOWED IN CLOSET WITH COMBUSTIBLES (COATS) |
|
| 01/19/2011 | ELECTRIC - SERVICE UPGRADE | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1) SEPERATE NEUTRALS AND GROUNDS AT ALL SUB PANELS 2) BOND ENCLOSURES 3) CORRECTLY IDENTIFY UNINSULATED NEUTRAL CONDUCTOR 4) BREAKERS TO BE LISTED FOR USE BY MANUFACTURE |
|
| 01/12/2011 | ELECTRIC - SERVICE UPGRADE | Not ready for Inspection | IVRS - Inspection :* 1) CALL AFTER SWING OVER OR REFEE WILL BE POSTED |
|
| 01/10/2011 | ELECTRIC - SERVICE UPGRADE | Partial Approval |