Inspection Status: Approved
Inspection History: INSP - INITIAL CODE ENFORCMENT
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/28/2011 | INSP - INITIAL CODE ENFORCMENT | Approved | VISITED SITE: TALKED WITH OCC. OF #129, NOT AWARE OF ISSUES, HE DID NOT MAKE COMPLAINT. DID ALLOW ME TO LOOK AROUND AT SERVICE. 1) BREAKERS NOT COMPATIBLE WITH SERVICE. 2) WEATHER HEAD TO SHORT. 3) 30 AMP. BREAKERS TO SMALL BE TODAY'S STANDARDS, NOT ENOUGH TO SERVICE ITEMS. 4) USING ZIP CORD TO SERVICE COOLER. 5) OPEN EXPOSED ROMEX 6) SERVICE LINE FROM 129 SERVICE PANEL TO UNIT 131 WAY TO SHORT. APPROX. 7' FROM GRADE, REQUIRES MIMINUM 12' 7) SUB PANELS SCREW IN FUSES OVER PROTECTED. 8) INTERIOR CONVENIENCE OUTLET 3 PRONG ON 2 WIRE SYSTEM. SHOWS OPEN GROUND UNDER TEST. 9) #135 HOT WATER TANK REPLACED WITH NEW, NO PERMIT SECURED. ALL ISSUES MENTIONED ABOVE CREATE A HAZARDOUS CONDITION. N/O/V TO BE ISSUED AFTER RESEARCH. (P.D.S.D). SEE COND. |