Case: T11DV06462

Parcel: 12007679A


Addresses:

3919 S 12TH AV

Inspection Status: Approved

Inspection History: INSP - FOLLOW UP CODE ENFORCE

Date Description Inspector Results Comments
08/29/2011 INSP - FOLLOW UP CODE ENFORCE Approved HAD CASE REVIEW BY THE DEVELOPMENT SERVICES THEY EXAMINED THE CASE HISTORY AND PHOTOS AND DETERMINED THAT THERE IS NO VIOLATION OF THE SERVICE PANELS.

HAD ADMINISTRATOR REVIEW CASE AND DETERMINED THAT THE COMPLAINT IS INVALIDED
WILL CLOSE CASE


CASE HISTORY
2007 THERE WAS A COMMERCIAL ALTERATION FOR TI SALON AND RETAIL PERMIT T07CM03170 FOR UNIT # 1 THAT WAS FINAL IN 06/06/2008. THE ELECTRICAL FINAL WAS IN 5-28-2008. C OF O WAS ISSUED IN 06/06/2008.
________________________________________________________________________
2009 PERMIT T09OT01916 C OF O: BEAUTY SALON WAS ISSUED IN 09-21-2009/ UNIT 1
_________________________________________________________________________
2010 RECONNECT; ELECTRIC; COMM PERMIT T10EL02443 FINAL IN 11/04/2010/ UNIT 3

IVRS - Inspection : 10-25-2010
See detailed listing on site.| 999*
1) WHERE DRYWALL HAS BEEN ADDED BOXES MORE THAN 1/4" BOX TO SURFACE 314.20
2) BATHROOM RECEPT TO BE GFCI PROTECTED
3) IDENTIFY AND LABEL SERVICES
4) USE APPROVED CONNECTORS FOR NM CABLE AT NEW SUB PANEL
5) USE CORRECT SIZED BONDING JUMPER

IVRS - Inspection : 11-01-2010
See detailed listing on site.| 999*
1) FILL UNUSED OPENING IN BOTTOM OF SERVICE PANEL
2) FINISH #3 (NEED ADDRESSES FOR SERVICES) AND #5 BOND JUMPER FOR FEEDER RACEWAY

IVRS - Inspection :*11-03-2011
1) ONLY ONE CONDUCTOR PER LUG

RECN CLEARED FOR #3 PER R. HOLLANDER / PERMIT FINAL 11-04-2011

____________________________________________________________________
2011 RECONNECT:ELECTRIC BUS. T11EL01910/ PERMIT FINAL IN 07/26/2011

7-22-2011 CHANGED FROM AP TO PARTIAL TO ALLOW FOR REINSPECTION. INSPECTOR TO VERIFY UNIT #3 WAS MISLABLED AS UNIT #1. CLEARANCE IS NEEDED FOR UNIT #3

7-29-2011 IVRS - Inspection :*
1) PLEASE CORRECT NUMBERS ON FRONT OF UNITS

RECN CLEARED FOR #1 PER D. SANTACRUZ 7-26-2011
RECN CLEARED FOR #3 PER D. SANTACRUZ 7-29-2011