Inspection History Details
Inspection Status: Approved
Inspection History: INSP - INITIAL CODE ENFORCMENT
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/18/2011 | INSP - INITIAL CODE ENFORCMENT | Approved | THERE HAS BEEN NEW ADDITION ATTACHED TO THE REAR OF THE DWELLING, ESTIMATE 11X 21 IS AN ADDITION PLUS PORCH. THE ADDITION IS BLOCK CONSTRUCTION WITH A WOOD FRAMED PORCH. THE ADDITION DOES HAVE POWER. I SAW NON-METALLIC SHEATHED ELECTRICAL CABLE IMBEDDED IN A MORTAR JOINT PROVIDING POWER TO AN EXTERIOR LIGHT FIXTURE. THERE IS ALSO NON-METALLIC SHEATHED ELECTRICAL CABLE RUNNING PARALLEL WITH THE 2X 4 RAFTERS AND ENTERING THE INTERIOR. THE CABLE IS #12 WITH YELLOW SHEATHING AND NOT APPROVED FOR OUTDOOR USE. THE CABLE IS SUPPORTED BY NAILS WHICH ARE BENT UPWARDS. THE H25 CLIPS ARE FASTENED WITH ROOFING NAILS. THERE IS A NEW ROOF MOUNTED A/C UNIT WITH A TUBULAR DISTRIBUTION DUCT WORK SYSTEM. THE MAIN DISCONNECT HAS A NEW ADDED CIRCUIT WITH LIQUID-TIGHT FLEXIBLE CONDUIT NOT PROPERLY STRAPPED. THE DWELLING UNIT IS NOT A RENTAL |