Inspection History Details
Inspection Status: Approved
Inspection History: INSP - INITIAL CODE ENFORCMENT
Case Number - T11DV04888
Inspection Description - INSP - INITIAL CODE ENFORCMENT
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/21/2011 | INSP - INITIAL CODE ENFORCMENT | Approved | VISITED SITE: CHILLER SYSTEM HOLDING, UP AND RUNNING. HAVE NO OTHER COMPLAINT CALLS FROM 6/27/11 COMPLIANT CLOSE/CASE. |
|
| 06/27/2011 | INSP - INITIAL CODE ENFORCMENT | Approved | VISITED SITE: NO MANAGEMENT ON SITE, OFFICE PHONE DISCONNECTED, VISITED #229, OCCUPANTS HOME, ENTERED UNIT FELT DECENT AS FAR AS TEMP. FELT AIR DUCTS, VENTS, HAS SEMI COLD AIR COMMING OUT OF VENTS. VISITED OTHER END OF BUILDING, OCCUPANT HOME, ALLOWED TO ENTER FELT GOOD, COLDER AIR COMMING FROM VENTS. CHILLER SYSTEM IS WORKING AT THIS TIME. NO VIOLATION. CLOSE/CASE. INSPECTOR NOTES: EX-MANAGER SHOWED TALKED WITH WITH EX-MANAGER, CONCURRED CHILLER SYSTEM HAS PROBLEM, HAS HAD T.R.S (CONTRACTOR) OUT. 1 COMPRESSOR DOWN. COMPRESSOR 2 WORKING, WATER TEMPS SUPPLY AND RETURN GOOD AT THIS TIME. COMPRESSOR 2 WORKING AT FULL CAPACITY. TALKED WITH T.R.S., JOSE. WENT OVER ISSUES, JOSE EXPLAINED ISSUES, CONTROL BOARD BAD NEEDS TO BE REPLACED, ALSO OIL PRESSURE SWITCH CUTS IN AND OUT DUE TO OVER HEATING, THERMO OVERLOAD, SWITCH REQUIRES MANUAL RESET, ONLY AFTER COMPRESSURE COOLS DOWN. THIS IS INTERMEDIATE PROBLEM. A/C ON A/C OFF. TALKED WITH MANAGER MICHAEL FROM 4100 E 29TH. AGREED TO MEET ON SITE THIS AFTERNOON. |