Case: T11DV02184

Parcel: 10408075P


Addresses:

4439 N ORACLE RD

Inspection Status: Approved

Inspection History: INSP - INITIAL CODE ENFORCMENT

Date Description Inspector Results Comments
04/04/2011 INSP - INITIAL CODE ENFORCMENT Approved TFD REQUEST FOR INSPECTION, INSP FOUND EQUIPMENT FIRE IN THE REPAIR OF THE COMMERCIAL STORE THE GOLFSMITH. EQUIPMENT TO MOVE AIR, PLACED UNDERNEATH A WORK BENCH WHICH ALSO INCLUDED AN ADDED RECEPTICLE TO THE BOX WAS OVERLOADED POSSIBLY ARCHED AND BURNED THE FAN BOX. FIRE DID NOT SPREAD OUTSIDE OF THE REPAIR ROOM, HOWEVER THE ENTIRE STORE RECEIVED HEAVY SMOKE THROUGHOUT. ELECTRICAL TO THE REPAIR ROOM WAS ISOLATED, THE BREAKERS WERE TAPED AND MARKED FOR NON USE. MANAGER HAD CALLED AN ELECTRICIAN PRIOR TO MY ARRIVAL AND WAS IN ROUTE. UPON INSPECTION AND WHILE SPEAKING TO FIRE INVESTIGATOR FOUND EXISTING GRID CEILING WHICH WAS METAL, SPACED GRID DID NOT PROPERLY CONTAIN THE HEAT AND OR SMOKE NOT ALLOWING THE EXISTING SPRINKLER HEAD TO GO OFF AND ACTUALLY CONTAIN THE FIRE AND SMOKE. WAYNE CUMMINGS FELT THAT IF THE ROOM HAD THE PROPER ACOUSTIC TILES THAT THE FIRE AND SOMOKE WOULD HAVE BEEN CONTAINED TO THE REPAIR ROOM. EXPLAINED TO THE MANAGER COREY THAT A NOV WOULD NOT BE ISSUED UNTIL RESEARCH WAS PERFORMD AND COMPLETED.