Permit: T11CM03962

Parcel: 12108066A


Addresses:

6161 E FAIRMOUNT ST

Inspection Status: Approved

Inspection History: FIRE - ALARM FINAL

Date Description Inspector Results Comments
07/23/2012 FIRE - ALARM FINAL Approved
07/12/2012 FIRE - ALARM FINAL Denied 1.) When testing duct detectors A/C units failed to shut down only the compressors not the fans.
2.) Need to reprogram alarm system so that only reset button is the only thing that resets the A/C units and dampers, can not have silence button resting systems.
3.) At FACP panel need to label all devices as to where they are located by name or map mounted by panel showing each device location by number.
4.) Need a breaker lock out on the fire alarm system in the electrical panel.