Inspection History: MECHANICAL - FINAL

Permit Number - T11CM03962

Inspection Description - MECHANICAL - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
08/22/2012 MECHANICAL - FINAL Approved IVRS - Inspection :*
08/21/2012 MECHANICAL - FINAL Denied NOT USE DUCT TAPE OUTDOORS. HEAT SENSOR NOT WORKING. MAKE UP AIR NOT WORKING. NEED CAPTURE AND CONTAINMENT TEST. AIR BALANCE OK
08/02/2012 MECHANICAL - FINAL Partial Approval ELECTRIC:
1) INSTALL FOR WALK IN BOX 300.7
2) FLUSH PANEL LABELING OR REST OF PREVIOUS ITEMS
07/20/2012 MECHANICAL - FINAL Partial Approval IVRS - Inspection :*
EXTEND ALL SEWER VENTS WITHIN 10' OF AN AIR INTAKE TO MIN 3'
REMOVE ABANDONED ELEC FITTINGS IN DISCONNECTS & SEAL OPENINGS
PERMANNITLY ID ALL EQUOPMENT ON ROOF
ALL GAS PIPING MUST BE BLOCKED & CLAMPED
07/12/2012 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*