Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/22/2012 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* | |
| 08/21/2012 | MECHANICAL - FINAL | Denied | NOT USE DUCT TAPE OUTDOORS. HEAT SENSOR NOT WORKING. MAKE UP AIR NOT WORKING. NEED CAPTURE AND CONTAINMENT TEST. AIR BALANCE OK | |
| 08/02/2012 | MECHANICAL - FINAL | Partial Approval | ELECTRIC: 1) INSTALL FOR WALK IN BOX 300.7 2) FLUSH PANEL LABELING OR REST OF PREVIOUS ITEMS |
|
| 07/20/2012 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :* EXTEND ALL SEWER VENTS WITHIN 10' OF AN AIR INTAKE TO MIN 3' REMOVE ABANDONED ELEC FITTINGS IN DISCONNECTS & SEAL OPENINGS PERMANNITLY ID ALL EQUOPMENT ON ROOF ALL GAS PIPING MUST BE BLOCKED & CLAMPED |
|
| 07/12/2012 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* |