Inspection History Details
Inspection Status: Partial Approval
Inspection History: MECHANICAL - HOODS
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/22/2012 | MECHANICAL - HOODS | Partial Approval | IVRS - Inspection :* | |
| 08/22/2012 | MECHANICAL - HOODS | Approved | IVRS - Inspection :* | |
| 08/21/2012 | MECHANICAL - HOODS | Denied | PROVIDE A PROTECTIVE COATING ON EXPOSED ARMAFLEX. DO NOT USE DUCT TAPE OUTDOORS. HEAT SENSOR NOT WORKING. MAKE UP AIR NOT WORKING. NEED CAPTURE AND CONTAINMENT TEST. AIR BALANCE OK | |
| 08/02/2012 | MECHANICAL - HOODS | Partial Approval | PROVIDE A CHAIN ON HINGE KIT. PROVIDE STERILIZATION TEST REPORT. BACKFLOW REPORTS OK. PROVIDE FREEZE PROTECTION AT OUTDOOR PIPING. SEAL OPEN KNOCKOUTS IN DISCONNECTS. PROVIDE A GREASE RECEPTOR AT EXHAUST FAN. PROVIDE AIR BALANCE REPORT | |
| 07/12/2012 | MECHANICAL - HOODS | Denied | IVRS - Inspection : See detailed listing on site.| 999* |