Permit: T11CM03962

Parcel: 12108066A


Addresses:

6161 E FAIRMOUNT ST

Inspection Status: Partial Approval

Inspection History: MECHANICAL - HOODS

Date Description Inspector Results Comments
08/22/2012 MECHANICAL - HOODS Partial Approval IVRS - Inspection :*
08/22/2012 MECHANICAL - HOODS Approved IVRS - Inspection :*
08/21/2012 MECHANICAL - HOODS Denied PROVIDE A PROTECTIVE COATING ON EXPOSED ARMAFLEX. DO NOT USE DUCT TAPE OUTDOORS. HEAT SENSOR NOT WORKING. MAKE UP AIR NOT WORKING. NEED CAPTURE AND CONTAINMENT TEST. AIR BALANCE OK
08/02/2012 MECHANICAL - HOODS Partial Approval PROVIDE A CHAIN ON HINGE KIT. PROVIDE STERILIZATION TEST REPORT. BACKFLOW REPORTS OK. PROVIDE FREEZE PROTECTION AT OUTDOOR PIPING. SEAL OPEN KNOCKOUTS IN DISCONNECTS. PROVIDE A GREASE RECEPTOR AT EXHAUST FAN. PROVIDE AIR BALANCE REPORT
07/12/2012 MECHANICAL - HOODS Denied IVRS - Inspection :
See detailed listing on site.| 999*