Permit: T11CM03962

Parcel: 12108066A


Addresses:

6161 E FAIRMOUNT ST


Inspection Status: Approved

Inspection History: PLUMBING - GAS PRESS TEST FNL

Permit Number - T11CM03962

Inspection Description - PLUMBING - GAS PRESS TEST FNL

Inspection Status - Approved

Date Description Inspector Results Comments
07/16/2012 PLUMBING - GAS PRESS TEST FNL Approved IVRS - Inspection :*
07/12/2012 PLUMBING - GAS PRESS TEST FNL Denied IVRS - Inspection :
See detailed listing on site.| 999*
07/02/2012 PLUMBING - GAS PRESS TEST FNL Partial Approval IVRS - Inspection :*
LEFT 2 GAS CARDS
AT WATER HEATER EXTEND DOUBLE WALL VENT DOWN BELOW CEILING
SECURE EXPANSION TANK AT SMALL WATER HEATER
SECURE VENTING
REPLACE T&P VALVE ON SMALL WATER HEATER
15 PSI TEST AT METER A NOT HOLDING PRESSURE
06/07/2012 PLUMBING - GAS PRESS TEST FNL Not ready for Inspection IVRS - Inspection :*
PROVIDE A PRESSURE GAUGE IN 1/10TH INCREMENTS 15LBS
06/04/2012 PLUMBING - GAS PRESS TEST FNL Not ready for Inspection IVRS - Inspection :*
1) STOVE DOES NOT FIT UNDER HOOD CORRECTLY
2) THE 2 LARGE UNITS GAS FLEX CONNECTORS NOT ADEQUATE FOR 90,000 BTU
3) BLOCK AND CLAMP GAS LINES ON ROOF
NOTE:
PAINT EXPOSED PVC WITH LATEX PAINT. EXTEND SEWER VENTS 2' ABOVE AIR INTAKES. PROVIDE A PRESSURE TEST FOR METER B