Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - GAS PRESS TEST FNL
Permit Number - T11CM03962
Inspection Description - PLUMBING - GAS PRESS TEST FNL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
07/16/2012 | PLUMBING - GAS PRESS TEST FNL | Approved | IVRS - Inspection :* | |
07/12/2012 | PLUMBING - GAS PRESS TEST FNL | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
07/02/2012 | PLUMBING - GAS PRESS TEST FNL | Partial Approval | IVRS - Inspection :* LEFT 2 GAS CARDS AT WATER HEATER EXTEND DOUBLE WALL VENT DOWN BELOW CEILING SECURE EXPANSION TANK AT SMALL WATER HEATER SECURE VENTING REPLACE T&P VALVE ON SMALL WATER HEATER 15 PSI TEST AT METER A NOT HOLDING PRESSURE |
|
06/07/2012 | PLUMBING - GAS PRESS TEST FNL | Not ready for Inspection | IVRS - Inspection :* PROVIDE A PRESSURE GAUGE IN 1/10TH INCREMENTS 15LBS |
|
06/04/2012 | PLUMBING - GAS PRESS TEST FNL | Not ready for Inspection | IVRS - Inspection :* 1) STOVE DOES NOT FIT UNDER HOOD CORRECTLY 2) THE 2 LARGE UNITS GAS FLEX CONNECTORS NOT ADEQUATE FOR 90,000 BTU 3) BLOCK AND CLAMP GAS LINES ON ROOF NOTE: PAINT EXPOSED PVC WITH LATEX PAINT. EXTEND SEWER VENTS 2' ABOVE AIR INTAKES. PROVIDE A PRESSURE TEST FOR METER B |