Inspection Status: Approved
Inspection History: PLUMBING - PROGRESS
| Date |
Description |
Inspector |
Results |
Comments |
| 07/30/2013 |
PLUMBING - PROGRESS |
|
Approved |
IVRS - Inspection :* |
| 07/30/2013 |
PLUMBING - PROGRESS |
|
Approved |
TERMINATE COOLER DRAIN W/ 1" - FOR FINAL PROVIDE AIR BALANCE REPORT STERILIZATION REPORT, BACKFLOW CERTIFICATION FOR IRRIGATION. DO NOT USE ZIP TIES TO SUPPORT EXHAUST DUCTS. SECURE FLEX DUCT WITH CONDUIT STRAPS. TERMINATE SECONDARY DRAIN TO A CONSPICUOUS LOCATION OR USE AN OVERFLOW SENSOR. DO NOT USE DUCT TAPE OUTDOORS. |