Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/16/2013 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 09/11/2013 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
| 09/11/2013 | ELECTRIC - FINAL | Denied | THIS IS AN AUTOMOTIVE GARAGE. WIRING SHALL COMPY W/ DRT 511 NEC. PLEASE RESCH ELECTRICAL INSP. HOIST DISCONNECTS REQUIRE READY ACCESS PER 430.107. DF OUTLET IS BELOW 18." MUST BE RAISED. |