Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
02/27/2012 MECHANICAL - FINAL Approved IVRS - Inspection :*
02/24/2012 MECHANICAL - FINAL Partial Approval IVRS - Inspection :*
1) OUTSIDE AIR REPORT AND DUCT SMOKE DETECTOR TEST REPORT OK, STILL WAITING ON COMPLETE AIR BALANCE REPORT
2) BATHROOM EXHAUST IS TO BE TIED TO SUPPLY FAN OR OTHER APPROVED MEANS OF INTERLOCK
02/23/2012 MECHANICAL - FINAL Not ready for Inspection IVRS - Inspection :*