Inspection History Details
Inspection Status: Partial Approval
Inspection History: ELECTRIC - ABOVE CEILING
Permit Number - T11CM03896
Inspection Description - ELECTRIC - ABOVE CEILING
Inspection Status - Partial Approval
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
03/07/2012 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1) FIRE STOPPING IN SERVER ROOM BY BLDG INSPECTOR 2) LETTER NEED CITY REVIEW |
|
03/07/2012 | ELECTRIC - ABOVE CEILING | Approved | ||
03/06/2012 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1) OK ROOMS 210, 211 VDV AND HALL LIGHTS 2) WAITING ON A/C DISCONNECT THAT IS NOT CODE COMPLIANT-HALL |
|
03/05/2012 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1) FINISH VDV AND HALL 2) OK POWER AND LIGHTS #202-211, 220-222 AND 213-218 |
|
03/02/2012 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1) FINISH VDV CABLING 2) OK LIGHTING AND POWER ROOMS 212-218 |
|
02/29/2012 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1) REPAIR AND REHANG EXIT SIGN IN HALL 2) OPEN JUNCTION BOX 3) VDV CABLING 300.11 4) NEED SUPPORT WIRE FOR EXIT LIGHT 5) A/C DISCONNECTS NOT CODE COMPLIANT AT TIME OF INSTALL 6) OK #201, 202, 203, CORRIDOR 201, 222,223 AND CORRIDOR 212 |