Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - ABOVE CEILING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/27/2012 | ELECTRIC - ABOVE CEILING | Approved | ||
| 02/13/2012 | ELECTRIC - ABOVE CEILING | Partial Approval | 18TH FLOOR OK | |
| 02/08/2012 | ELECTRIC - ABOVE CEILING | Denied | EXISTING DUCTWORK, PUMPS & ELECTRIC APPARENTLY DONE WITHOUT PERMITS AS SUPPORTS, TERMINATIONS, ETC. DO NOT MEET CODE. 1) FLEX DUCT TO BE SUPPORTED 4' O.C. 2) ALL WIRING, INCLUDING LOW VOLTAGE MUST BE SUPPORTED OFF GRID & PROPERLY TERMINATED INSIDE LISTED J-BOXES OR EQUIPEMENT. |
|
| 02/06/2012 | ELECTRIC - ABOVE CEILING | Not ready for Inspection |