Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - ROUGH, SOIL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/01/2012 | PLUMBING - ROUGH, SOIL | Approved | IVRS - Inspection :* | |
| 02/17/2012 | PLUMBING - ROUGH, SOIL | Partial Approval | 1) WATER LINE STUBBED DOWN WITH BACKFLOW OK 2) ABS AND PVC MAY NOT BE INTERMINGLED 3) TRANSITION CEMENT MAY ONLY BE USED WHERE THE BLDG DRAIN CONNECTS TO THE BLDG SEWER, MISSION BANDS WOULD BE THE CORRECT TRANSITION 4) BLAKE TEES ARE NOT LISTED TO BE USED AS A TEST FITTING BELOW GRADE, USE A DIRECTIONAL FITTING FOR TESTING. WILL ACCEPT PHOTO 5) OK TO BACKFILL |
|
| 02/16/2012 | PLUMBING - ROUGH, SOIL | Cancelled | CANCELLED PER CONTRACTOR ED #602-663-7379 | |
| 02/16/2012 | PLUMBING - ROUGH, SOIL | Not ready for Inspection | IVRS - Inspection :* 1) CALLED AND LEFT MSG., YOU ASKED FOR AN AM INSPECTION |