Permit: T11CM03842

Parcel: 12201024J


Addresses:

3920 E GRANT RD

Inspection Status: Approved

Inspection History: MECHANICAL - HOODS

Date Description Inspector Results Comments
03/20/2012 MECHANICAL - HOODS Approved IVRS - Inspection :*
1) 2ND LAYER OF FIRE WRAP OK
03/15/2012 MECHANICAL - HOODS Partial Approval IVRS - Inspection :*
1) 1ST LAYER OF FIRE WRAP OK
2) ON 2ND LAYER, BANDING TO BE WITHIN 1 1/2" OF EACH EDGE AND 10 1/2" SPACING
03/09/2012 MECHANICAL - HOODS Partial Approval IVRS - Inspection :*
1) SMOKE TEST ON COMPLETED GREASE DUCT OK
2) 2ND LAYER OF FIRE WRAP NOT INSALLED CORRECTLY, NO OVER LAP AND NOT ENOUGH BENDS
03/08/2012 MECHANICAL - HOODS Partial Approval IVRS - Inspection :*
1) SMOKE TEST ON 2 SECTIONS GREASE DUCT OK
2) 1ST LAYER FIRE WRAP ON 2 SECTIONS GREASE DUCT OK, OK TO 2ND LAYER
3) 1ST 6' OF UPPER SECTION