Inspection History: FIRE SPKLR - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/27/2012 | FIRE SPKLR - FINAL | Approved | ||
| 06/07/2012 | FIRE SPKLR - FINAL | Denied | In the service/work shop area insulation seating on top of sprinklers need to keep 1 away from sprinkler heads. In the service/work shop area next to the hot water heater and sink sprinkler coverage blocked by conduit. 2nd floor office northeast corner closet, sprinkler head buried in the wall needs to be min 4" away from wall. 2nd floor office middle office northeast side sprinkler cage broken repair or replace. Need to install sprinkler coverage in the riser room. |
|
| 05/16/2012 | FIRE SPKLR - FINAL | Denied | Need to install sprinkler coverage under new attached parking cover (carport) on Westside of building. |