Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
Permit Number - T11CM03792
Inspection Description - ELECTRIC - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
03/08/2012 | ELECTRIC - INTERMEDIATE | Approved | ||
02/10/2012 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) TIGHTEN LOOSE FITTINGS 2) MISSING COVER SCREWS 406.3 3) CORRECTLY IDENTIFY 1G GROUNDS IN RECEPT BOXES 4) NEED AUTHORIZATION FOR USE OF M/C AND FLEX CONDUIT AT ?, PLANS CALL FOR CONDUIT 5) IN WALL ELECTRIC WORK INSTALLED AND COVERED WITHOUT INSPECTIONS 6) CIRCUITS ON PLANS DIFFER FROM CIRCUITS INSTALLED 7) WAITING ON LIGHTS FOR MAIN COUNTER-FILL UNUSED OPENINGS 8) WORK HAS BEEN ENERGIZED AND IN USE FOR MORE THAN 30 DAYS WITHOUT INSPECTIONS |