Permit: T11CM03788

Parcel: 12417168C


Addresses:

840 S SANTA RITA AV

Inspection Status: Approved

Inspection History: MECHANICAL - ABOVE CEILING

Date Description Inspector Results Comments
03/12/2013 MECHANICAL - ABOVE CEILING Approved IVRS - Inspection :*
03/07/2013 MECHANICAL - ABOVE CEILING Not ready for Inspection IVRS - Inspection :*
1) FLEX DUCT NOT PROPERLY SUPPORTED, MAX SPACING 5' ON HANGERS, MINIMUM WIDTH OF HANGER IS 1.5"
2) PROVIDE MINIMUM 2" BEADED COLLARS AT ALL FLEX DUCT CONNECTIONS.
3) PROVIDE SEISMIC SUPPORT AT ALL T-BAR REGISTERS
02/14/2013 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection :*