Inspection History Details
Inspection Status: Approved
Inspection History: BUILDING - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/27/2012 | BUILDING - FINAL | Approved | IVRS - Inspection :* | |
| 01/18/2012 | BUILDING - FINAL | Partial Approval | IVRS - Inspection :* | |
| 01/13/2012 | BUILDING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) OLD SERVICE IS A SERVICE USE ONLY-CANNOT USE AS SUB PANEL 2) GROUNDING ELECTRODE TO BE CONTINOUS WITH IRREVERSABLE SPLICE AND BOND METAL RACEWAYS PER 250.64 3) USE BREAKERS LISTED BY INSTRUCTIONS AT MAIN PANEL 110.3 (B) 4) USE SUITABLE MOUNTING HARDWARE 5) ONLY ONE CONDUCTOR PER LUG TERMINAL 110.14 6) CANNOT USE SHEET METAL THREAD SCREWS 250.8 7) LABELING TO BE PER 690.17 8) CORRECTLY IDENTIFY GROUNDED CONDUCTOR AT WEATHER HEAD 9) MINIMUM GROUNDING ELECTRODE CONDUCTOR SIZE IS #8 250.66 10) JUNCTION BOX OVER FILLED 11) CORRECTLY SUPPORT PV CONDUCTOR 12) RAISE RACEWAYS OFF OF ROOF FOR DRAINAGE 13) PROPERLY BOND PV RAILS AND MODULES 690.4/ + PER MGF INSTRUCTIONS 14) GROUNDING CONDUCTOR UNDER SIZED 15) ROOF LAYOUT NOT PER PLANS |