Inspection History: BUILDING - FINAL

Date Description Inspector Results Comments
01/27/2012 BUILDING - FINAL Approved IVRS - Inspection :*
01/18/2012 BUILDING - FINAL Partial Approval IVRS - Inspection :*
01/13/2012 BUILDING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) OLD SERVICE IS A SERVICE USE ONLY-CANNOT USE AS SUB PANEL
2) GROUNDING ELECTRODE TO BE CONTINOUS WITH IRREVERSABLE SPLICE AND BOND METAL RACEWAYS PER 250.64
3) USE BREAKERS LISTED BY INSTRUCTIONS AT MAIN PANEL 110.3 (B)
4) USE SUITABLE MOUNTING HARDWARE
5) ONLY ONE CONDUCTOR PER LUG TERMINAL 110.14
6) CANNOT USE SHEET METAL THREAD SCREWS 250.8
7) LABELING TO BE PER 690.17
8) CORRECTLY IDENTIFY GROUNDED CONDUCTOR AT WEATHER HEAD
9) MINIMUM GROUNDING ELECTRODE CONDUCTOR SIZE IS #8 250.66
10) JUNCTION BOX OVER FILLED
11) CORRECTLY SUPPORT PV CONDUCTOR
12) RAISE RACEWAYS OFF OF ROOF FOR DRAINAGE
13) PROPERLY BOND PV RAILS AND MODULES 690.4/ + PER MGF INSTRUCTIONS
14) GROUNDING CONDUCTOR UNDER SIZED
15) ROOF LAYOUT NOT PER PLANS