Permit: T11CM03766

Parcel: 132191230


Addresses:

2001 E IRVINGTON RD


Inspection Status: Approved

Inspection History: MECHANICAL - HOODS

Permit Number - T11CM03766

Inspection Description - MECHANICAL - HOODS

Inspection Status - Approved

Date Description Inspector Results Comments
04/02/2012 MECHANICAL - HOODS Approved
03/08/2012 MECHANICAL - HOODS Partial Approval IVRS - Inspection :*
1) 1ST LAYER FIRE WRAP OK
2) CLEAN ALL SLAG FROM DUCT CLEANOUT OPENING IN ORDER TO PROVIDE LIQUID TIGHT SEAL
03/07/2012 MECHANICAL - HOODS Partial Approval IVRS - Inspection :*
1) OK TO COMPLETE 1ST LAYER OF FIRE WRAP ON GREASE DUCT
03/06/2012 MECHANICAL - HOODS Cancelled CANCELLED PER CONTACTOR ED #602-663-7379
03/06/2012 MECHANICAL - HOODS Not ready for Inspection IVRS - Inspection :*
03/01/2012 MECHANICAL - HOODS Partial Approval IVRS - Inspection :*
1) DUCT SMOKE TEST ON GREASE DUCT OK
2) 1ST LAYER FIRE WRAP OK
3) 2ND LAYER FIRE WRAP WILL LOOK AT LATER DATE