Inspection History: BUILDING - FINAL

Date Description Inspector Results Comments
05/30/2012 BUILDING - FINAL Approved IVRS - Inspection :*
05/25/2012 BUILDING - FINAL Not ready for Inspection IVRS - Inspection :*
1) NEED RECEPT LEFT SIDE OF RANGE
2) NEED ANTI TIP FOR NEW RANGE
3) SHEATHING TO BE 1/4" INTO BOX
4) DRYER CIRCUIT NOT CODE COMPLIANT OR AS PER PLANS
5) CLEAN EXCESS FOREIGN MATERIAL AND DIRT FROM PANEL
6) SEAL UNUSED PORTION OF HOLE IN BACK OF PANEL WITH A NON COMBUSTIBLE PRODUCT
7) LABEL CIRCUITS-GENERAL LABELING NOT ALLOWED
8) BREAKER AMPACITY FOR NM CABLE TO BE PER 334.80
9) DISH WASHER/DISPOSAL A MULTI WIRE CIRCUIT NEEDS HANDLE TIE
10) MISSING SMOKE DETECTORS PER PLANS