Permit: T11CM03738

Parcel: 11711102A


Addresses:

101 E PENNINGTON ST

Inspection Status: Approved

Inspection History: FIRE SPKLR - OH PIPING & HYDRO

Date Description Inspector Results Comments
07/31/2012 FIRE SPKLR - OH PIPING & HYDRO Approved
07/19/2012 FIRE SPKLR - OH PIPING & HYDRO Partial Approval 2nd floor inspection
200 PSI test for 2 hours approved.
1. Coverage needed in the chase room
2. Add coverage in patio (varies) room.
3. North west bedroom add coverage in closet
4. In kitchen correct coverage head to far 8' 6" off wall.
05/11/2012 FIRE SPKLR - OH PIPING & HYDRO Partial Approval Basement and 1st floor 200 PSI for 2 hours approved.
In Basement correct the following areas:
1. Cold storage room
2. In electrical room or main panel area
3. By stairwell southeast corner.