Permit: T11CM03727

Parcel: 10503033A

Inspection Status: Approved

Inspection History: PLUMBING - INTERMEDIATE

Permit Number - T11CM03727

Inspection Description - PLUMBING - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
03/30/2012 PLUMBING - INTERMEDIATE Approved IVRS - Inspection :*
03/27/2012 PLUMBING - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
1) ABS IS TO BE SUPPORTED AT EACH CHANGE OF DIRECTION OR ELEVATION, AND AT THE END OF BRANCHES, THRU NO MORE THAN 4' BETWEEN HANGERS
2) SUPPORT VERTICAL PIPE
3) ISOLATE ABS FROM METAL STUDS
4) TEST ALL PIPING THRU THE ROOF
5) JIM CAPS MAY NOT BE USED IN LIEU OF BLIND PLUGS
6) SUPPORT EXISTING CAST IRON AND COPPER AS REQUIRED BY TABLE 3-2