Permit: T11CM03727

Parcel: 10503033A

Inspection Status: Approved

Inspection History: ELECTRIC - ABOVE CEILING

Permit Number - T11CM03727

Inspection Description - ELECTRIC - ABOVE CEILING

Inspection Status - Approved

Date Description Inspector Results Comments
05/09/2012 ELECTRIC - ABOVE CEILING Approved IVRS - Inspection :*
04/23/2012 ELECTRIC - ABOVE CEILING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) SUPPORT M/C UP OFF GRID AND PER CODE OVER 6' FROM LUMINIER 12" + 6'
2) SUPPORT WIRES NEEDED FOR ALL CANS
3) BOX OVERFILLED
4) FILL UNUSED BOX OPENINGS
5) SUPPORT EMT PER CODE
6) LARGE JUNCTION BOX NOT WIRED AT THIS TIME
7) VDV CABLING TO BE PER 725.3 & 8, 800.3 & 24 AND 300.11
8) STILL NEED LIGHTING PLANS
03/15/2012 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*