Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - ABOVE CEILING
Permit Number - T11CM03727
Inspection Description - ELECTRIC - ABOVE CEILING
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/09/2012 | ELECTRIC - ABOVE CEILING | Approved | IVRS - Inspection :* | |
| 04/23/2012 | ELECTRIC - ABOVE CEILING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) SUPPORT M/C UP OFF GRID AND PER CODE OVER 6' FROM LUMINIER 12" + 6' 2) SUPPORT WIRES NEEDED FOR ALL CANS 3) BOX OVERFILLED 4) FILL UNUSED BOX OPENINGS 5) SUPPORT EMT PER CODE 6) LARGE JUNCTION BOX NOT WIRED AT THIS TIME 7) VDV CABLING TO BE PER 725.3 & 8, 800.3 & 24 AND 300.11 8) STILL NEED LIGHTING PLANS |
|
| 03/15/2012 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* |