Inspection Status: Approved
Inspection History: MECHANICAL - ABOVE CEILING
Permit Number - T11CM03707
Inspection Description - MECHANICAL - ABOVE CEILING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
03/19/2013 | MECHANICAL - ABOVE CEILING | Approved | PER MECH FINAL | |
03/06/2013 | MECHANICAL - ABOVE CEILING | Partial Approval | IVRS - Inspection :* OK FOR CEILING TILES ALL AREAS LEVEL 2 AND 3 | |
02/27/2013 | MECHANICAL - ABOVE CEILING | Partial Approval | IVRS - Inspection :* | |
01/31/2013 | MECHANICAL - ABOVE CEILING | Partial Approval | 2nd floor room 20485 ok for sheet rock 1st floor area b ok for ceiling tiles except in old field office | |
01/30/2013 | MECHANICAL - ABOVE CEILING | Partial Approval | IVRS - Inspection :* | |
01/25/2013 | MECHANICAL - ABOVE CEILING | Partial Approval | 4th floor finish angle iron at fire damper in corrider 3 vav boxes not accessible 4th floor ok for ceiling tiles 4th floor | |
01/24/2013 | MECHANICAL - ABOVE CEILING | Partial Approval | OK FOR CEILING TILES 2ND FLOOR AREA A EXCEPT FOR ROOM 20363 AND AT VAV BOXES IN CENTRAL CORRIDOR | |
01/17/2013 | MECHANICAL - ABOVE CEILING | Denied | IVRS - Inspection : See detailed listing on site.| 999* SOME VAV BOXES STILL NOT ACCESSIBLE AS DOCUMENTED ON 09/10/12, 11/06/12, 12/18/12. DO NOT INSTALL CEILING TILES UNTIL THESE ISSUES ARE ADDRESSED. |
|
01/10/2013 | MECHANICAL - ABOVE CEILING | Partial Approval | 100 PSI HYDRO TEST ON REMAINING HOT WATER & CHILLED WATER PIPING ON 1ST FLOOR OK TO INSULATE | |
01/07/2013 | MECHANICAL - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1ST FLOOR AREA D OK TO COVER MECHANICAL 4TH FLOOR ROOMS 41011 TO 41030 OK COVER MECHANICAL |
|
12/28/2012 | MECHANICAL - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1ST FLOOR LOBBY OK TO COVER HARD LID.OK TO COVER MECHANICAL IN O.R. ROOMS 2ND FLOOR #2-14 3RD FLOOR #1,2,3,4,6 |
|
12/18/2012 | MECHANICAL - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1ST FLOOR AREA A OK FOR CEILING TILES. 2ND FLOOR VAV 5T-5-41 IN CORRIDOR NOT ACCESSIBLE. 2ND FLOOR STERILE CORRIDOR OK TO COVER | |
11/15/2012 | MECHANICAL - ABOVE CEILING | Partial Approval | mechanical ok to cover in existing exam rooms | |
10/24/2012 | MECHANICAL - ABOVE CEILING | Partial Approval | CHWS&CHWR 16107 CORREDOR END OF RUN AND STRARTS AT EXAM ROOM 16311. HWS & HWR STARTS AT EXAM ROOM 16302 AND END AT WORK AREA 16332 . TEST OK. | |
10/23/2012 | MECHANICAL - ABOVE CEILING | Partial Approval | IVRS - Inspection :* | |
10/18/2012 | MECHANICAL - ABOVE CEILING | Partial Approval | TEST ON STEAM PIPING AND CONDENSAT MAINS ONLY ON 2ND FOOR( TRAPS NOT TESTED) | |
10/12/2012 | MECHANICAL - ABOVE CEILING | Partial Approval | level 2 area c toilet rooms abv hard lids ok | |
09/25/2012 | MECHANICAL - ABOVE CEILING | Partial Approval | SUPPLY & EXHAUST IN 3RD FLOOR RESTROOMS OK TO COVER | |
09/21/2012 | MECHANICAL - ABOVE CEILING | Partial Approval | RESCHEDULE RESTROOMS AFTER INSULATION IS FINISHED | |
09/10/2012 | MECHANICAL - ABOVE CEILING | Partial Approval | MAINTAIN CLEAR ACCESS TO SERVICE ALL VAV BOXES SPRINKLER PIPE BLOCKING ACCESS AT ST5-7. SUPPLY AND EXHAUST IN ALL RESTROOMS AND JANITOR CLOSETS ON 2ND FLOOR OK | |
08/24/2012 | MECHANICAL - ABOVE CEILING | Not ready for Inspection | CANCEL BY CHRIS COLE | |
08/22/2012 | MECHANICAL - ABOVE CEILING | Partial Approval | PEDIATRICS | |
07/26/2012 | MECHANICAL - ABOVE CEILING | Partial Approval | IVRS - Inspection :* | |
07/02/2012 | MECHANICAL - ABOVE CEILING | Partial Approval | IVRS - Inspection :* STARTING HARD LIDS ON 2ND FLOOR |
|
06/18/2012 | MECHANICAL - ABOVE CEILING | Not ready for Inspection | IVRS - Inspection :* | |
06/05/2012 | MECHANICAL - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 2ND FLOOR RETURN AIR RISERS IN O.R. OK TO COVER WORK PROGRESSING ON 1ST + 3RD FLOORS |
|
05/22/2012 | MECHANICAL - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1) FIRE DAMPER ANGLES OK |
|
05/16/2012 | MECHANICAL - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1) SUSPENDED ROUGH DUCT 2ND FLOOR AND 3RD FLOOR PROGRESSING |